Section 31 TrinkwV requires systematic Legionella testing only where several conditions coincide. The drinking water must be supplied in a commercial or public activity; the building must have a large hot-water installation and showers or other outlets that produce aerosols. One- and two-family homes are excluded from this particular rule. A large installation exists where a storage or central instantaneous heater holds more than 400 litres, or a pipe between heater outlet and draw-off point holds more than three litres; circulation pipe volume is excluded from the latter calculation.
Use and installation | Minimum testing interval under § 31 |
Commercial supply only, all technical triggers met | At least every three years. |
Public supply, all technical triggers met | At least annually; a health authority may allow a longer interval under the statutory conditions. |
Newly commissioned installation subject to the rule | First test three to twelve months after commissioning. |
No large hot-water installation or no aerosol-generating outlet | No automatic § 31 systematic Legionella test on that basis; other water-quality duties still apply. |
A simple “every commercial building must test every three years” rule is therefore inaccurate. A hotel with guest showers, an office without showers and a small shop with an electric point-of-use heater may fall into different categories. Map the actual system and its use before ordering a sampling programme. Sampling and analysis belong with a laboratory approved for drinking-water testing under the ordinance; the sampling points must represent the system.