Condition | What it means |
Large hot-water system | Storage or central instantaneous heater holds more than 400 litres, or at least one pipe from the heater to a draw-off point holds more than three litres; circulation volume is excluded from that pipe calculation. |
Aerosol-generating outlet | The system serves a shower or another outlet where water is aerosolised. |
Building type | The installation is outside a one- or two-family house. |
Supply from a building installation | Statutory minimum |
Commercial activity, without public activity | At least every three years. |
Public activity | At least once a year, unless the health authority allows up to three years after three consecutive clean annual tests and the other conditions in § 31(3) are met. The extension is excluded for specified higher-risk facilities. |
Newly commissioned installation covered by § 31 | First investigation within three to twelve months of commissioning. |